How To Fix Double Tapping At Circuit Breakers

By
Home Inspector with Structure Tech Home Inspections

Double tapped circuit breakers are one of the most common electrical defects that I find while doing home inspections in Minneapolis and Saint Paul, and they're usually one of the easiest defects to correct.  Today I'll explain what double tapping is, when it is and isn't a problem, why it's a problem, and how to correct this condition.

I didn't consult with an attorney before writing this article, so I feel like I should add a disclaimer:  This blog is only an overview of what an electrician might do.  Don't try to do any electrical work if you're not qualified.

Definition: I don't know of any official definition of a 'double tap'.  This is just what us home inspectors say when two wires are connected under one screw or terminal inside an electric panel.  Sometimes this refers to two wires at one circuit breaker, other times it refers to two wires connected under one screw at the neutral bar.  Today I'll be focusing on improperly double tapped circuit breakers.

When it's NOT problem: Double tapped wiring is ok if the circuit breaker is designed for two wires.  If a circuit breaker is designed for two wires, it will say so right on the circuit breaker, and the terminal of the circuit breaker will be designed to hold two wires in place.  The circuit breaker shown below is designed to accept two wires, and I highlighted and blew up the portion of the label that tells me that two wires can be attached.  This is acceptable.  To my knowledge, the only manufacturers  that make circuit breakers that can be double tapped are Square D and Cutler Hammer... but not all of their circuit breakers can be double tapped.

Square D Breaker

When it IS a problem: This is a problem when the circuit breaker isn't designed for two wires.  The label on the circuit breaker will clearly state this.

Double Tap Single Pole Label

Why it's a problem: If the circuit breaker isn't designed to hold two wires, the wires could come loose at some point in the future, even if they feel very tight today.  Loose wires can lead to overheating, arcing, and possibly a fire.

How to fix: The fixes I'm going to list below are a few common ways of dealing with double tapped circuit breakers.

Pig Tail This is usually the easiest and best repair.  The offending wires simply get disconnected from the circuit breaker, connected to a single wire with a wire nut, and that single wire gets connected to the circuit breaker.   Now, I know what you're thinking: "What's so tough about that?"  The answer is nothing.  This is a quick and easy fix.

Pig Tail

Different Circuit Breaker Another simple repair would be to replace the circuit breaker with a type that is designed for two wires, as long as the panel is designed for it.

If there are more problems going on besides just a double tap, the repair might get more involved.  For instance, if a homeowner finished off a basement and added a circuit for the basement bedroom on to the circuit breaker for the bathroom receptacles, simply adding a pig tail for the wires wouldn't be a proper repair, because the bathroom receptacles can't be on a shared circuit.   In this case, the wires would need to be split off on to two separate circuit breakers.  There are a few ways to do this.

Add A Circuit Breaker If there is room in the panel, another circuit breaker can be added, and the wires split off to the two different circuit breakers.

Two Circuit Breakers

Install A Tandem Breaker If the electric panel is designed to use tandem breakers, and a tandem breaker can be properly used in lieu of the offending circuit breaker, this is another acceptable fix.  Some people refer to tandem breakers as half-height or half-size breakers.  This is basically a way to install two circuit breakers in one slot.

Tandem Breaker

If a panel will accept tandem breakers, it will say so inside the panel, and the specific locations where tandem breakers can be used will be identified.  A panel may allow all tandem breakers, notandem breakers, or some tandem breakers.  The photo below shows a panel that allows some.  As you can see, eight more circuits could be added to this panel, as there are currently no tandem breakers being used.

Tandem Breakers Label

When none of the above solutions are possible, the repair might involve replacement of the panel with a larger one, or the addition of a subpanel.  This would obviously get much more expensive.

 

close

Re-Bloggged 3 times:

Re-Blogged By Re-Blogged At
  1. Wallace S. Gibson, CPM 01/19/2010 04:56 AM
  2. Dan Edward Phillips 12/19/2011 12:00 PM
  3. Dan Edward Phillips 01/09/2012 02:51 AM
Spam prevention

Accessibility option: listen to a question and answer it!

To submit the form,
drag the balloons to the circle on the side.

Type below the answer to what you hear. Numbers or words, lowercase:

Topic:
Home Buying
Location:
Minnesota Hennepin County Minneapolis
Groups:
ASHI
Ask the Home Inspector
Home Inspectors across the country
Home Inspector's Corner
Professional Home Inspectors
Tags:
how to correct
double tapping
double tapped circuit breaker
double tapped circuit
double tapped
double tap
double lugging
double lug

Comments 24 New Comment

Anonymous
Post a Comment
Spam prevention

Accessibility option: listen to a question and answer it!

To submit the form,
drag the music-note to the circle on the side.

Type below the answer to what you hear. Numbers or words, lowercase:

Rainer
84,150
Mike Parks
Inspector
Residential Building Inspectors

Another example would be in a manufactured home.

You could have a 200 AMP disconnect on a pole feeding the home with 4/0, then under the home in a box reduce the wire to feed a 100 AMP panel inside.

That wire would be a tap. The 100 AMP breaker inside protects the tap.

January 25, 2010 06:30 AM
Anonymous #21
Anonymous
Samanthacarter

At Inspection.com, our vision is to become the leading market for un-biased home inspection leads in the world. To this end, we need to quickly and promptly help consumers make decisions about choosing an inspector, and ensuring that all inspectors on our network put their best foot forward. This includes helping inspectors with their web and marketing presence, while ensuring that those inspectors that are qualified and provide good service, rise to the top.

July 14, 2012 03:37 AM
Anonymous #22
Anonymous
paul jackson
I am a licensed electrician and I wish home inspectors would take the time to actually try and understand what you are explaining. It is very obvious when you open a panel and see the screw with the two "humps" on either side of the screw head you know that breaker is rated for handling 2 wires that are of the same properties and size. I have bought and sold many houses and been in many fights with home inspectors who thought they knew more than me until I pulled out my license and code book and taught them a thing or two. I wanted to point out that in your explanation of the breake type that can only handle one wire you circles "1 pole" on the breaker. That only tells some one that it is a single pole breaker not how many wires can be installed under the screw. IF the breaker doesn't say 2 wires or have the "humps" it can't have two wires under the screw and must be spliced to a single wire going to the breaker.
March 24, 2014 03:08 PM
Anonymous #23
Anonymous
keith
i agree with paul jackson's explaination. 1 pole doesn't mean the breaker can only handle 1 wire.
March 26, 2014 11:53 PM
Rainmaker
229,301
Reuben Saltzman
Minneapolis Home Inspections
Structure Tech Home Inspections

Yes, that photo doesn't belong.  One pole is not the same as one conductor.  I originally wrote this post in 2009, then posted in here in 2010.  I don't know what I was thinking back then.  

March 27, 2014 04:01 AM
Anonymous
Post a Comment
Spam prevention

Accessibility option: listen to a question and answer it!

To submit the form,
drag the clip to the circle on the side.

Type below the answer to what you hear. Numbers or words, lowercase:

Rainmaker
229,301

Reuben Saltzman

Minneapolis Home Inspections
Ask me a question
*
*
*
Spam prevention

Accessibility option: listen to a question and answer it!

To submit the form,
drag the robot to the circle on the side.

Type below the answer to what you hear. Numbers or words, lowercase:

Additional Information

Home inspection topics in the Minneapolis / Saint Paul area.